Chapter 2 Fault Management System 197
Business Communications Manager - Management User Guide
User action: Check cable connections to batteries.
Alarm severity: Minor
Trap-type: Warning
Logs: None
Event ID: 301300 Message: UPS internal temperature over limit
User action: Make sure that there is adequate clearance around the UPS, and
that the UPS ventilation ports are not blocked. Allowing the UPS to
continue to operate in this condition can damage the UPS. If the
condition persists, contact APC Support for assistance. http://
www.apc.com/go/direct/index.cfm?tag=support.
Alarm severity: Minor
Trap-type: Warning
Logs: None
Event ID: 301301 Message: UPS battery charger failure
User action: An internal hardware failure exists. Contact APC Support for
assistance. http://www.apc.com/go/direct/index.cfm?tag=support
Alarm severity: Minor
Trap-type: Warning
Logs: None
Event ID: 301302 Message: UPS on bypass: severe DC imbalance overload
User action: An internal hardware failure exists. Contact APC Support for
assistance. http://www.apc.com/go/direct/index.cfm?tag=support
Alarm severity: Minor
Trap-type: Warning
Logs: None
Event ID: 301303 Message: UPS on bypass: output voltage outside limits
User action: The UPS has switched automatically to bypass mode because its
output voltage was too high. Contact APC Support for assistance.
http://www.apc.com/go/direct/index.cfm?tag=support.
Alarm severity: Minor
Trap-type: Warning
Logs: None
Event ID: 301304 Message: UPS on bypass: top module fan needs repair
User action: A hardware failure has caused the UPS to switch to bypass
operation. Since the UPS cannot support its load if a power failure
occurs, correct the failure as soon as possible. Contact APC Support
for assistance. http://www.apc.com/go/direct/index.cfm?tag=support
Alarm severity: Critical
Trap-type: Error
Logs: None
Event ID: 301400 Message: Base module fan needs repair
UPS
(Uninterruptible
power supply)
Return to table: Component ID (alarm)/eventSource (trap) summary