192 Chapter 2 Fault Management System
P0609330 2.0
Event ID: 200007 Message: UPS on battery: Large momentary spike
User action: This event can be caused by poor power quality (i.e. power
fluctuation). Decrease the sensitivity of the UPS. If the condition
persists, contact an electrician to analyze your utility power.
Alarm severity: Minor
Trap-type: Warning
Logs: None
Event ID: 200008 Message: UPS on battery: Simulated power failure
User action: Wait for this test to complete.
Alarm severity: Minor
Trap-type: Warning
Logs: None
Event ID: 200200 Message: UPS enabling SmartBoost
User action: If this event occurs frequently, decrease the Low Transfer Voltage of
your UPS. If the condition persists, contact an electrician to analyze
your utility power.
Alarm severity: Warning
Trap-type: Information
Logs: None
Event ID: 200301 Message: Low battery condition
User action: The UPS cannot continue to use its battery power to support its
equipment load. The remaining runtime equals, or is less than, the
runtime defined by its "Low Battery" setting. Consider upgrading to a
UPS that provides more runtime. You can use the APC UPS
Selector page to identify the UPS that best meets your system's
requirements. http://www.apc.com/go/direct/
index.cfm?tag=selectors
Alarm severity: Minor
Trap-type: Warning
Logs: None
Event ID: 200400 Message: UPS runtime calibration cancelled
User action: No action required.
Alarm severity: Warning
Trap-type: Information
Logs: None
Event ID: 200401 Message: UPS runtime calibration cancelled by user
User action: No action required.
Alarm severity: Warning
Trap-type: Information
Logs: None
Event ID: 200402 Message: UPS runtime calibration aborted by power failure
UPS
(Uninterruptible
power supply)
Return to table: Component ID (alarm)/eventSource (trap) summary