Avaya BCM Management Guia do Utilizador Página 197

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 488
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 196
Chapter 2 Fault Management System 193
Business Communications Manager - Management User Guide
User action: Retry the calibration when power is restored
Alarm severity: Warning
Trap-type: Information
Logs: None
Event ID: 200403 Message: UPS unable to perform runtime calibration: Capacity < 100%
User action: The UPS battery capacity is less than 100%, probably because of
recent battery operation of the UPS. Wait for the batteries to
recharge and then retry the runtime calibration.
Alarm severity: Minor
Trap-type: Warning
Logs: None
Event ID: 200700 Message: UPS enabling SmartTrim
User action: If this event occurs frequently, increase the High Transfer Voltage of
your UPS. If the condition persists, contact an electrician to analyze
your utility power.
Alarm severity: Warning
Trap-type: Information
Logs: None
Event ID: 201301 Message: UPS on bypass: user set via software or panel
User action: The front panel or a software command was used to put the UPS into
bypass mode, typically for maintenance. Since the UPS cannot
support its load if a power failure occurs, return the UPS to online
operation as soon as possible.
Alarm severity: Warning
Trap-type: Information
Logs: None
Event ID: 201302 Message: UPS system is in maintenance bypass set by switch
User action: The switch at the UPS was used to put the UPS into bypass mode,
typically for maintenance. Since the UPS cannot support its load if a
power failure occurs, return the UPS to on-line operation as soon as
possible.
Alarm severity: Warning
Trap-type: Information
Logs: None
Event ID: 203100 Message: UPS module failed
User action: Replace the failed module.
Alarm severity: Critical
Trap-type: Error
Logs: None
Event ID: 203200 Message: Main intelligence module removed
User action: This is the first step in replacing a failed module. Continue with the
replacement
UPS
(Uninterruptible
power supply)
Return to table: Component ID (alarm)/eventSource (trap) summary
Vista de página 196
1 2 ... 192 193 194 195 196 197 198 199 200 201 202 ... 487 488

Comentários a estes Manuais

Sem comentários