
Troubleshooting a Data Link Connection Problem
5-17
Troubleshooting an MCT1 Connection
This section assumes that you have isolated a problem to an MCT1 (multichannel
T1) connection. If not, refer to Chapter 2 to determine whether these instructions
apply to your problem.
A includes instructions on reading MCT1 log messages.
Do the following if the connection is MCT1:
1. Filter the log to display only messages from the MCT1 entity running on
the slots experiencing the problem. The Technician Interface command is
log -fftwid -eMCT1 -s
<slot_no.>
Example
If you are filtering events from Slots 3 and 4, you enter
log -fftwid -eMCT1 -s3 -s4
2.
Check the following MCT1 MIB entries by entering the following
Technician Interface commands:
get wfDrivers.14.0
Or, use the following Quick Get path to this attribute:
wfSoftwareConfig➔wfDrivers➔wfMunichLoad.
get wfLinkModules.17.0
Or, use the following Quick Get path to this attribute:
wfSoftwareConfig➔wfLinkModules➔wfMCT1E1Load.
3. Make sure that the Line Type and Line Coding supplied by the T1
provider match the associated settings in the MCT1 configuration.
4. Make sure the DS0s (Directory Service 0) channels match at both the
router and the central office.
5. Watch the LEDs in the back of the MCT1. If the Sync LED keeps
flashing, the LBO (line build out; impedance or resistance on a line) is not
in sync. Ask the T1 carrier if you should set it to long haul or short haul,
and configure the LBO parameter accordingly.
Note: Appendix A includes instructions on reading MCT1 log messages.
Comentários a estes Manuais